What are the safety fire prevention measures for stage lighting?

From the fire in Hunan Sanxiang audio market to the fire in Xinjiang Grand Theater, and even the Changchun KTV fire in Henan, etc., fires frequently occur in the near future, and fire prevention should be started from the root cause. Therefore, for the performing arts market, stage lighting fire protection design is very important. of. Then, how can the stage lighting fire protection design be qualified as a fire safety inspection?

Stage lighting

What are the safety fire prevention measures for stage lighting?

1. Reasonable selection of lamp types

In explosion-prone mixtures or where it is prone to generate explosive media, an integral explosion-proof device should be used. For corrosive gases and particularly humid places, sealed or moisture-proof luminaires shall be used, and the components shall be treated with anti-corrosion treatment. Floodlights can be used in hot and dusty places (such as steelmaking, iron making, steel rolling, etc.). Outdoor lighting can be enclosed lamps or open lamps with fire lamp holders.

2, should properly install lighting, decorative lighting

(1) The distance between the lamps and the combustibles shall not be less than 50 cm (the tungsten halogen lamps shall be greater than 50 cm), and the height of the ground shall not be less than 2 m. When the height is lower than this, protective equipment shall be installed. It is not advisable to stack flammable materials under the bulb;

(2) The protective cover of the luminaire must be intact, and it is strictly forbidden to cover the luminaire with paper, cloth or other combustible materials;

(3) All concealed and surface mounted lamps on the flammable ceiling should not be too large, and should be dominated by incandescent or fluorescent lamps; concealed lamps and their heating accessories should have good heat dissipation conditions around them. The conductors of the stage concealed lanterns, dance floor lamps and flammable ceiling lamps shall be laid with steel pipes or flame-retardant hard plastic casings; the wires near the tungsten halogen lamps shall be made of heat-resistant insulating sheaths; There should be a rubber ring protection through the keel;

(4) Selecting a low-temperature ballast with reliable quality, it is not allowed to directly fix the ballast with high temperature rise on objects such as combustible large-flower plates, and its capacitance and capacity must be consistent with the lamp;

(5) Class 0, Class 10 explosion hazardous places (0 level area refers to explosive gas, level 10 area refers to explosive dust), when opening type lamps are used to make wall-mounted alcove, the access door should be outside the wall. Open and ensure good ventilation; the side that is illuminated indoors should be sealed with double glazing. The horizontal distance from the door and the window frame is not less than 3 meters, and the horizontal distance from the air outlet is not less than 5 meters.

3. Reasonable control of electrical lighting

The lighting currents should each have their own branch circuit and should not be connected after the main power switch. Short circuit protection facilities shall be provided for each branch circuit. In order to avoid accidents caused by overload and heat, some important places and inflammable and explosive materials must also be equipped with overload protection devices. Non-explosion-proof lighting distribution boxes and control switches are strictly forbidden to be used in Class 0 and Class 10 explosion hazardous areas. Minimize the joint after the switchboard, and the disk surface should be well grounded.

4, strict lighting voltage level and load

The lighting voltage is generally 220 volts, the supply voltage of portable lighting fixtures should not exceed 36 volts, and in wet areas should not exceed 12 volts, and autotransformers are prohibited. Power outlets below 36 volts and above 220 volts should have significant differences and markings. The number of lamps in a branch circuit should not exceed 20, the civil lighting current should be less than 15 amps, and the industrial use should be less than 20 amps. The wire size is determined by the amount of load (each socket is measured with a load of 2 to 3 amps). The three-phase four-wire lighting circuit should also be balanced with three-phase load.

Accident lighting fixtures should be located in places prone to accidents, main entrances and exits of buildings, important workplaces, etc., and marked with obvious color markings for timely and convenient activation. Accident lighting fixtures cannot be of a slow start type (such as ballast starters, etc.). Accident lighting fixtures should be powered by an independent emergency battery to ensure that the normal power system is properly opened when unaffected.

Earphones is one of our important products , both the in ear headfphones and Earphones With Mic have advantages as follow :

The sound quality of the best in Ear Headphones is amazing.

Military level unite voices more pure.

Great sound experience.

Two voices exports more stereo sound.

These earphones with mic have the mic on the wire and the wired earphones works great.All metal building cavity make a more powerful sound shock.Wide dynamic range;Dual bass sound unit design, a broader range.

Excellent bass response;Connect to all MP3 players and digital audio device.

These Good Quality Earphones have real deep heavy base, excellent high frequency and no distortion. And these earphones are comfortable , completely fit to the shape of the ears.

Earphones

Ear Headphones, Earphones With Mic, Good Quality Earphones

Hebei Baisiwei Import&Export Trade Co., LTD. , https://www.baisiweicable.com

Posted on